Republished vendor advisory. This ICSA is a verbatim republication of Siemens ProductCERT SSA-614723 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA…
General Recommendations: As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals. Additional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity
Additional Resources: For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Credit: Siemens ProductCERT
From CISA's machine-readable CSAF 2.0 advisory (JSON).
| CVE | Weakness | CVSS v3 | Details |
|---|---|---|---|
| CVE-2025-30174 | CWE-125 Out-of-bounds Read | 7.5 High |
CVE-2025-30174 Affected products contain a out of bound read buffer overflow vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to cause a denial of service condition. Mitigation: In non-networked scenarios/deployments block TCP ports 4002 and 4004 on machines with UMC installed. In addition if no RT server machines are used, port 4004 can be blocked completely No fix planned: Currently no fix is planned Vendor fix: Update to V2.15.1.1 or later version ↗ Affected, fixed & timelineAffected:
Vendor fix: Update to V4.0 or later version Vendor fix: Update UMC to V2.15.1.1 or later compatible version https://support.industry.siemens.com/cs/ww/en/view/109987708/ |
| CVE-2025-30175 | CWE-787 Out-of-bounds Write | 7.5 High |
CVE-2025-30175 Affected products contain a out of bound write buffer overflow vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to cause a denial of service condition. Mitigation: In non-networked scenarios/deployments block TCP ports 4002 and 4004 on machines with UMC installed. In addition if no RT server machines are used, port 4004 can be blocked completely No fix planned: Currently no fix is planned Vendor fix: Update to V2.15.1.1 or later version ↗ Affected, fixed & timelineAffected:
Vendor fix: Update to V4.0 or later version Vendor fix: Update UMC to V2.15.1.1 or later compatible version https://support.industry.siemens.com/cs/ww/en/view/109987708/ |
| CVE-2025-30176 | CWE-125 Out-of-bounds Read | 7.5 High |
CVE-2025-30176 Affected products contain a out of bound read buffer overflow vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to cause a denial of service condition. Mitigation: In non-networked scenarios/deployments block TCP ports 4002 and 4004 on machines with UMC installed. In addition if no RT server machines are used, port 4004 can be blocked completely No fix planned: Currently no fix is planned Vendor fix: Update to V2.15.1.1 or later version ↗ Affected, fixed & timelineAffected:
Vendor fix: Update to V4.0 or later version Vendor fix: Update UMC to V2.15.1.1 or later compatible version https://support.industry.siemens.com/cs/ww/en/view/109987708/ |
Scores and weakness types are as CISA or the republishing vendor stated them in this advisory; the linked CVE pages carry the independently enriched CVSS and SSVC assessments.
No coverage found in monitored research blogs or news feeds.
| CVE | CVSS | Affected |
|---|---|---|
| CVE-2025-30174 | 7.5 High | Siemens SIMATIC PCS neo V4.1 A vulnerability has been identified in SIMATIC PCS neo V4.1 (All versions), SIMATIC PCS neo V5.0 (All versions), SINEC NMS (All versions < V4.0), SIN… |
| CVE-2025-30175 | 7.5 High | Siemens SIMATIC PCS neo V4.1 A vulnerability has been identified in SIMATIC PCS neo V4.1 (All versions), SIMATIC PCS neo V5.0 (All versions), SINEC NMS (All versions < V4.0), SIN… |
| CVE-2025-30176 | 7.5 High | Siemens SIMATIC PCS neo V4.1 A vulnerability has been identified in SIMATIC PCS neo V4.1 (All versions), SIMATIC PCS neo V5.0 (All versions), SINEC NMS (All versions < V4.0), SIN… |
Named by the advisory itself. Each CVE links to its tracked detail page.