No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
Credit: Rockwell Automation
From CISA's machine-readable CSAF 2.0 advisory (JSON).
| CVE | Weakness | CVSS v3 | Details |
|---|---|---|---|
| CVE-2025-9041 | CWE-20 Improper Input Validation | 7.5 High |
A security issue exists due to improper handling of CIP Class 32's request when a module is inhibited on the 5094-IF8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle. Mitigation: Rockwell Automation recommends users upgrade to V2.012 or later. The update can be downloaded from Rockwell Automation's website. ↗ Mitigation: Rockwell Automation also recommends users follow their published Security Best Practices. ↗ Affected, fixed & timelineAffected:
|
| CVE-2025-9042 | CWE-20 Improper Input Validation | 7.5 High |
A security issue exists due to improper handling of CIP Class 32's request when a module is inhibited on the 5094-IY8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle. Mitigation: Rockwell Automation recommends users upgrade to V2.012 or later. The update can be downloaded from Rockwell Automation's website. ↗ Mitigation: Rockwell Automation also recommends users follow their published Security Best Practices. ↗ Affected, fixed & timelineAffected:
|
Scores and weakness types are as CISA or the republishing vendor stated them in this advisory; the linked CVE pages carry the independently enriched CVSS and SSVC assessments.
No coverage found in monitored research blogs or news feeds.
| CVE | CVSS | Affected |
|---|---|---|
| CVE-2025-9041 | 8.7 High | Rockwell Automation FLEX 5000 I/O A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IF8 device. It causes the module to… |
| CVE-2025-9042 | 8.7 High | Rockwell Automation FLEX 5000 I/O A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IY8 device. It causes the module to… |
Named by the advisory itself. Each CVE links to its tracked detail page.
Each vendor links to its Known Exploited Vulnerabilities catalog page. Only vendors that appear in the KEV catalog are listed, either because the publication cites one of their KEV entries or because it names them directly.