ICSA-25-140-07: Schneider Electric Galaxy VS, Galaxy VL, Galaxy VXL (Update A) ↗ source

May 20, 2025 CISA ICS Advisory

Summary

Schneider Electric is aware of a vulnerability disclosed on the Erlang/OTP's SSH Server component used Schneider Electric Galaxy VS, VL, and VXL.Many vendors, including Schneider Electric, embed the Erlang/OTP's SSH Server in their offers.The Galaxy VS, Galaxy VL, Galaxy VXL products are 3-phase UPS for data centers and other business critical applications.Failure to apply the mitigation provided below may risk unauthenticated remote code execution (RCE), which could impact the monitoring capabilities of the UPS and potential UPS operation. CVE-2025-32433: Erlang/OTP is a set of libraries for the Erlang programming language. Prior to versions OTP-27.3.3, OTP-26.2.5.11, and OTP-25.3.2.20, a SSH server may allow an attacker to perform unauthenticated remote code execution (RCE). By exploiting a flaw in SSH protocol message handling, a malicious actor could gain unauthorized access to affected systems and execute arbitrary commands without valid credentials. This issue is patched in versions OTP-27.3.3, OTP-26.2.5.11, and OTP-25.3.2.20. A temporary workaround involves disabling the SSH server or to prevent access via firewall rules.

Advisory Details CISA ICS CSAF feed

Advisory ID
ICSA-25-140-07
Status
Final · version 3.0.0
Initial release
2025-05-13
Last revised
2025-09-24 (3 revisions)
Vendor
Schneider Electric
Critical infrastructure sectors
Commercial Facilities, Critical Manufacturing, Energy
Deployed
Worldwide
Vendor headquarters
France

Republished vendor advisory. This ICSA is a verbatim republication of Schneider Electric CPCERT SEVD-2025-133-05 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory.…

General Security Recommendations: We strongly recommend the following industry cybersecurity best practices. https://www.se.com/us/en/download/document/7EN52-0390/ * Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. * Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. * Place all controllers in locked cabinets and never leave them in the “Program” mode. * Never connect programming software to any network other than the network intended for that device. * Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. * Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. * Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. * When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.

For More Information: This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process. Customers should use appropriate patching methodologies when applying these patches to their systems. We strongly recommend the use of back-ups and evaluating the impact of these patches in a Test and Development environment or on an offline infrastructure. Contact Schneider Electric's Customer Care Center if you need assistance removing a patch. For further information related to cybersecurity in Schneider Electric's products, visit the company's cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp

About Schneider Electric: Schneider's purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and sustainability for all. We call this Life Is On. Our mission is to be the trusted partner in Sustainability and Efficiency. We are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart industries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep domain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation, software and services, delivering digital twins to enable profitable growth for our customers. We are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries to ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our meaningful purpose of a sustainable future for all.

Vulnerability Details: A vulnerability disclosed by Erlang/OTP's SSH Server impacts SSH component used on the Schneider Electric Galaxy VS, Galaxy VL, Galaxy VXL. CVE ID: CVE-2025-32433 Additional information about the vulnerability CVE-2025-32433 can be found in the https://github.com/erlang/otp/security/advisories/GHSA-37cp-fgq5-7wc2.

Credit: Schneider Electric CPCERT

Affected products (3)
  • Galaxy VS — <=6.118.0, 6.123.0
  • Galaxy VL — <=18.5.0, 18.10.0
  • Galaxy VXL — <=15.21.0, 15.29.0
Revision history (3)
  • 2025-09-24 — v3.0.0: Added missing CVE and CWE
  • 2025-09-09 — v2.0.0: Remediations are now available for Galaxy VS, Galaxy VL, and Galaxy VXL
  • 2025-05-13 — v1.0.0: Original Release

From CISA's machine-readable CSAF 2.0 advisory (JSON).

Vulnerabilities as Stated by the Advisory

CVEWeaknessCVSS v3Details
CVE-2025-32433 KEV CWE-306 Missing Authentication for Critical Function 10.0 Critical CVE-2025-32433
Erlang/OTP is a set of libraries for the Erlang programming language. Prior to versions OTP-27.3.3, OTP-26.2.5.11, and OTP-25.3.2.20, a SSH server may allow an attacker to perform unauthenticated remote code execution (RCE). By exploiting a flaw in SSH protocol message handling, a malicious actor could gain unauthorized access to affected systems and execute arbitrary commands without valid credentials. This issue is patched in versions OTP-27.3.3, OTP-26.2.5.11, and OTP-25.3.2.20. A temporary workaround involves disabling the SSH server or to prevent access via firewall rules.

Mitigation: If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: 1. Log on to the NMC4 via the Web Interface. Once logged into the system, navigate to the Console settings … ↗

Vendor fix: Version 6.123.0 of Galaxy VS includes a fix for this vulnerability and is available through your local FSR by contacting Schneider Electric's Customer Care Center.

Vendor fix: Version 18.10.0 of Galaxy VL includes a fix for this vulnerability and is available through your local FSR by contacting Schneider Electric's Customer Care Center.

Affected, fixed & timeline

Affected:

  • Galaxy VS <=6.118.0
  • Galaxy VL <=18.5.0
  • Galaxy VXL <=15.21.0

Fixed in:

  • Galaxy VS 6.123.0
  • Galaxy VL 18.10.0
  • Galaxy VXL 15.29.0

Vendor fix: Version 15.29.0 of Galaxy VXL includes a fix for this vulnerability and is available through your local FSR by contacting Schneider Electric's Customer Care Center.

Scores and weakness types are as CISA or the republishing vendor stated them in this advisory; the linked CVE pages carry the independently enriched CVSS and SSVC assessments.

News Coverage

No coverage found in monitored research blogs or news feeds.

CVEs Referenced in This Publication

CVECVSSAffected
CVE-2025-32433 10.0 Critical Erlang Erlang/OTP Erlang Erlang/OTP SSH server contains a missing authentication for critical function vulnerability. This could allow an attacker to execute arbitrary…

Named by the advisory itself. Each CVE links to its tracked detail page.

Vendors Named in This Publication

Each vendor links to its Known Exploited Vulnerabilities catalog page. Only vendors that appear in the KEV catalog are listed, either because the publication cites one of their KEV entries or because it names them directly.