CyberzSOC

Publication detail
← Back to advisories & guidance

ICSA-25-226-27: Rockwell Automation ArmorBlock 5000 I/O - Webserver ↗ source

August 14, 2025 CISA ICS Advisory

Summary

Successful exploitation of these vulnerabilities could allow an attacker to predict session numbers or perform privileged actions. CVE-2025-7773: A security issue exists within the 5032 16pt Digital Configurable module's webserver. The webserver's session number increments at an interval that correlates to the last two consecutive login session interval, making it predictable. CVE-2025-7774: A security issue exists within the 5032 16pt Digital Configurable module's webserver. Intercepted session credentials can be used within a three minute timeout window, allowing unauthorized users to perform privileged actions.

Advisory Details CISA ICS CSAF feed

Advisory ID
ICSA-25-226-27
Status
Final · version 1
Initial release
2025-08-14
Last revised
2025-08-14
Vendor
Rockwell Automation
Critical infrastructure sectors
Critical Manufacturing
Deployed
Worldwide
Vendor headquarters
United States

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

Do not click web links or open attachments in unsolicited email messages.

Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.

Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

Credit: Rockwell Automation

Affected products (3)
  • 5032-CFGB16M12P5DR — <=1.011
  • 5032-CFGB16M12DR — <=1.011
  • 5032-CFGB16M12M12LDR — <=1.011

From CISA's machine-readable CSAF 2.0 advisory (JSON).

Vulnerabilities as Stated by the Advisory

CVEWeaknessCVSS v3Details
CVE-2025-7773 CWE-863 Incorrect Authorization 8.6 High A security issue exists within the 5032 16pt Digital Configurable module's webserver. The webserver's session number increments at an interval that correlates to the last two consecutive login session interval, making it predictable.

Mitigation: Rockwell Automation recommends users update the corrected version if possible. If users using the affected software are not able to upgrade the version, security best practices should be applied. ↗

Affected, fixed & timeline

Affected:

  • 5032-CFGB16M12P5DR <=1.011
  • 5032-CFGB16M12DR <=1.011
  • 5032-CFGB16M12M12LDR <=1.011
CVE-2025-7774 CWE-287 Improper Authentication 8.6 High A security issue exists within the 5032 16pt Digital Configurable module's webserver. Intercepted session credentials can be used within a three minute timeout window, allowing unauthorized users to perform privileged actions.

Mitigation: Rockwell Automation recommends users update the corrected version if possible. If users using the affected software are not able to upgrade the version, security best practices should be applied. ↗

Affected, fixed & timeline

Affected:

  • 5032-CFGB16M12P5DR <=1.011
  • 5032-CFGB16M12DR <=1.011
  • 5032-CFGB16M12M12LDR <=1.011

Scores and weakness types are as CISA or the republishing vendor stated them in this advisory; the linked CVE pages carry the independently enriched CVSS and SSVC assessments.

News Coverage

No coverage found in monitored research blogs or news feeds.

CVEs Referenced in This Publication

CVECVSSAffected
CVE-2025-7773 8.8 High Rockwell Automation 5032-CFGB16M12P5DR A security issue exists within the 5032 16pt Digital Configurable module’s web server. The web server’s session number increments at an interval that…
CVE-2025-7774 8.8 High Rockwell Automation 5032-CFGB16M12P5DR A security issue exists within the 5032 16pt Digital Configurable module’s web server. Intercepted session credentials can be used within a 3-minute …

Named by the advisory itself. Each CVE links to its tracked detail page.

Vendors Named in This Publication