Republished vendor advisory. This CISA CSAF advisory was converted from Schneider Electric CPCERT's CSAF advisory.
General Security Recommendations: We strongly recommend the following industry cybersecurity best practices. https://www.se.com/us/en/download/document/7EN52-0390/ * Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. * Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. * Place all controllers in locked cabinets and never leave them in the “Program” mode. * Never connect programming software to any network other than the network intended for that device. * Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. * Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. * Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. * When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
For More Information: This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process. For further information related to cybersecurity in Schneider Electric’s products, visit the company’s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
About Schneider Electric: At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment. We provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries. We are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values. www.se.com
Credit: Marlon Schumacher, Alex Armstrong (LLNL); Vishal Madipadga (SNL)
From CISA's machine-readable CSAF 2.0 advisory (JSON).
| CVE | Weakness | CVSS v3 | Details |
|---|---|---|---|
| CVE-2024-37036 | CWE-787 Out-of-bounds Write | 9.8 Critical |
CVE-2024-37036 CWE-787: Out-of-bounds Write vulnerability exists that could result in an authentication bypass when sending a malformed POST request and particular configuration parameters are set. Vendor fix: Firmware version C3414-500-S02K5_P9 of SAGE RTU includes a fix for these vulnerabilities and is available for download here:https://www.se.com/us/en/download/document/C3414-500-S02K5_P9_Firmware/ ↗ Affected, fixed & timelineAffected:
Fixed in:
|
| CVE-2024-37037 | CWE-22 Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') | 8.1 High |
CVE-2024-37037 CWE-22: Improper Limitation of a Pathname to a Restricted Directory (‘Path Traversal’) vulnerability exists that could allow an authenticated user with access to the device’s web interface to corrupt files and impact device functionality when sending a crafted HTTP request. Vendor fix: Firmware version C3414-500-S02K5_P9 of SAGE RTU includes a fix for these vulnerabilities and is available for download here:https://www.se.com/us/en/download/document/C3414-500-S02K5_P9_Firmware/ ↗ Affected, fixed & timelineAffected:
Fixed in:
|
| CVE-2024-37038 | CWE-276 Incorrect Default Permissions | 7.5 High |
CVE-2024-37038 CWE-276: Incorrect Default Permissions vulnerability exists that could allow an authenticated user with access to the device’s web interface to perform unauthorized file and firmware uploads when crafting custom web requests. Vendor fix: Firmware version C3414-500-S02K5_P9 of SAGE RTU includes a fix for these vulnerabilities and is available for download here:https://www.se.com/us/en/download/document/C3414-500-S02K5_P9_Firmware/ ↗ Affected, fixed & timelineAffected:
Fixed in:
|
| CVE-2024-37039 | CWE-252 Unchecked Return Value | 5.9 Medium |
CVE-2024-37039 CWE-252: Unchecked Return Value vulnerability exists that could cause denial of service of the device when an attacker sends a specially crafted HTTP request. Vendor fix: Firmware version C3414-500-S02K5_P9 of SAGE RTU includes a fix for these vulnerabilities and is available for download here:https://www.se.com/us/en/download/document/C3414-500-S02K5_P9_Firmware/ ↗ Affected, fixed & timelineAffected:
Fixed in:
|
| CVE-2024-37040 | CWE-120 Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') | 5.4 Medium |
CVE-2024-37040 CWE-120: Buffer Copy without Checking Size of Input (‘Classic Buffer Overflow’) vulnerability exists that could allow a user with access to the device’s web interface to cause a fault on the device when sending a malformed HTTP request. Vendor fix: Firmware version C3414-500-S02K5_P9 of SAGE RTU includes a fix for these vulnerabilities and is available for download here:https://www.se.com/us/en/download/document/C3414-500-S02K5_P9_Firmware/ ↗ Affected, fixed & timelineAffected:
Fixed in:
|
| CVE-2024-5560 | CWE-125 Out-of-bounds Read | 5.3 Medium |
CVE-2024-5560 CWE-125: Out-of-bounds Read vulnerability exists that could cause denial of service of the device’s web interface when an attacker sends a specially crafted HTTP request. Vendor fix: Firmware version C3414-500-S02K5_P9 of SAGE RTU includes a fix for these vulnerabilities and is available for download here:https://www.se.com/us/en/download/document/C3414-500-S02K5_P9_Firmware/ ↗ Affected, fixed & timelineAffected:
Fixed in:
|
Scores and weakness types are as CISA or the republishing vendor stated them in this advisory; the linked CVE pages carry the independently enriched CVSS and SSVC assessments.
No coverage found in monitored research blogs or news feeds.
| CVE | CVSS | Affected |
|---|---|---|
| CVE-2024-37036 | 9.8 Critical | Schneider Electric Sage 1410 CWE-787: Out-of-bounds Write vulnerability exists that could result in an authentication bypass when sending a malformed POST request and particular … |
| CVE-2024-37037 | 8.1 High | Schneider Electric Sage 1410 CWE-22: Improper Limitation of a Pathname to a Restricted Directory (‘Path Traversal’) vulnerability exists that could allow an authenticated user wi… |
| CVE-2024-37038 | 7.5 High | Schneider Electric Sage 1410 CWE-276: Incorrect Default Permissions vulnerability exists that could allow an authenticated user with access to the device’s web interface to perfo… |
| CVE-2024-37039 | 5.9 Medium | Schneider Electric Sage 1410 CWE-252: Unchecked Return Value vulnerability exists that could cause denial of service of the device when an attacker sends a specially crafted HTTP… |
| CVE-2024-37040 | 5.4 Medium | Schneider Electric Sage 1410 CWE-120: Buffer Copy without Checking Size of Input (‘Classic Buffer Overflow’) vulnerability exists that could allow a user with access to the devic… |
| CVE-2024-5560 | 5.3 Medium | Schneider Electric Sage 1410 CWE-125: Out-of-bounds Read vulnerability exists that could cause denial of service of the device’s web interface when an attacker sends a specially … |
Named by the advisory itself. Each CVE links to its tracked detail page.
Each vendor links to its Known Exploited Vulnerabilities catalog page. Only vendors that appear in the KEV catalog are listed, either because the publication cites one of their KEV entries or because it names them directly.