ICSA-24-193-15: Siemens SINEMA Remote Connect Server ↗ source

July 11, 2024 CISA ICS Advisory

Summary

SINEMA Remote Connect Server before V3.2 HF1 is affected by multiple vulnerabilities. Siemens has released a new version for SINEMA Remote Connect Client and recommends to update to the latest version. CVE-2024-39567: The system service of affected applications is vulnerable to command injection due to missing server side input sanitation when loading VPN configurations. This could allow an authenticated local attacker to execute arbitrary code with system privileges. CVE-2024-39568: The system service of affected applications is vulnerable to command injection due to missing server side input sanitation when loading proxy configurations. This could allow an authenticated local attacker to execute arbitrary code with system privileges. CVE-2024-39569: The system service of affected applications is vulnerable to command injection due to missing server side input sanitation when loading VPN configurations. This could allow an administrative remote attacker running a corresponding SINEMA Remote Connect Server to execute arbitrary code with system privileges on the client system.

Advisory Details CISA ICS CSAF feed

Advisory ID
ICSA-24-193-15
Status
Final · version 1
Initial release
2024-07-09
Last revised
2024-07-09
Vendor
Siemens
Critical infrastructure sectors
Multiple
Deployed
Worldwide
Vendor headquarters
Germany

Republished vendor advisory. This CISA CSAF advisory was converted from Siemens ProductCERT's CSAF advisory.

General Recommendations: As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals. Additional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity

Additional Resources: For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories

Credit: Siemens ProductCERT

Affected products (1)
  • SINEMA Remote Connect Client — <V3.2_HF1

From CISA's machine-readable CSAF 2.0 advisory (JSON).

Vulnerabilities as Stated by the Advisory

CVEWeaknessCVSS v3Details
CVE-2024-39567 CWE-77 Improper Neutralization of Special Elements used in a Command ('Command Injection') 7.8 High CVE-2024-39567
The system service of affected applications is vulnerable to command injection due to missing server side input sanitation when loading VPN configurations. This could allow an authenticated local attacker to execute arbitrary code with system privileges.

Vendor fix: Update to V3.2 HF1 or later version ↗

Affected, fixed & timeline

Affected:

  • SINEMA Remote Connect Client <V3.2_HF1
CVE-2024-39568 CWE-77 Improper Neutralization of Special Elements used in a Command ('Command Injection') 7.8 High CVE-2024-39568
The system service of affected applications is vulnerable to command injection due to missing server side input sanitation when loading proxy configurations. This could allow an authenticated local attacker to execute arbitrary code with system privileges.

Vendor fix: Update to V3.2 HF1 or later version ↗

Affected, fixed & timeline

Affected:

  • SINEMA Remote Connect Client <V3.2_HF1
CVE-2024-39569 CWE-77 Improper Neutralization of Special Elements used in a Command ('Command Injection') 6.6 Medium CVE-2024-39569
The system service of affected applications is vulnerable to command injection due to missing server side input sanitation when loading VPN configurations. This could allow an administrative remote attacker running a corresponding SINEMA Remote Connect Server to execute arbitrary code with system privileges on the client system.

Vendor fix: Update to V3.2 HF1 or later version ↗

Affected, fixed & timeline

Affected:

  • SINEMA Remote Connect Client <V3.2_HF1

Scores and weakness types are as CISA or the republishing vendor stated them in this advisory; the linked CVE pages carry the independently enriched CVSS and SSVC assessments.

News Coverage

No coverage found in monitored research blogs or news feeds.

CVEs Referenced in This Publication

CVECVSSAffected
CVE-2024-39567 7.8 High Siemens SINEMA Remote Connect Client A vulnerability has been identified in SINEMA Remote Connect Client (All versions < V3.2 HF1). The system service of affected applications is vulnera…
CVE-2024-39568 7.8 High Siemens SINEMA Remote Connect Client A vulnerability has been identified in SINEMA Remote Connect Client (All versions < V3.2 HF1). The system service of affected applications is vulnera…
CVE-2024-39569 6.6 Medium Siemens SINEMA Remote Connect Client A vulnerability has been identified in SINEMA Remote Connect Client (All versions < V3.2 HF1). The system service of affected applications is vulnera…