Summary

Successful exploitation of this vulnerability may allow an attacker to access credentials used for access to the application. CVE-2024-0912: Under certain circumstances the Microsoft Internet Information Server (IIS) used to host the C●CURE 9000 Web Server will log Microsoft Windows credential details within logs. There is no impact to non-web service interfaces C●CURE 9000 or prior versions.

Advisory Details CISA ICS CSAF feed

Advisory ID
ICSA-24-135-03
Status
Final · version 1
Initial release
2024-05-14
Last revised
2024-05-14
Vendor
Johnson Controls
Critical infrastructure sectors
Critical Manufacturing
Deployed
Worldwide
Vendor headquarters
Ireland

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely.

Credit: Johnson Controls

Affected products (1)
  • Software House C●CURE 9000 — v3.00.2

From CISA's machine-readable CSAF 2.0 advisory (JSON).

Vulnerabilities as Stated by the Advisory

CVEWeaknessCVSS v3Details
CVE-2024-0912 CWE-532 Insertion of Sensitive Information into Log File 7.7 High Under certain circumstances the Microsoft Internet Information Server (IIS) used to host the C●CURE 9000 Web Server will log Microsoft Windows credential details within logs. There is no impact to non-web service interfaces C●CURE 9000 or prior versions.

Mitigation: Johnson Controls recommends the following:

Vendor fix: Update Software House C●CURE 9000 to version 3.00.2 CU02 or 3.00.3

Mitigation: Change the password for the impacted windows accounts.

Affected, fixed & timeline

Affected:

  • Software House C●CURE 9000 v3.00.2

Mitigation: Delete the api.log log file (or remove instances of passwords from the log file with a text editor) located at "C:\Program Files (x86)\Tyco\victorWebServices\victorWebsite\Logs"

Mitigation: For more detailed mitigation instructions, please see Johnson Controls Product Security Advisory JCI-PSA-2024-04 v1

Mitigation: Aligning with CISA recommendations, Johnson Controls recommends taking steps to minimize risks to all building automation systems.

Scores and weakness types are as CISA or the republishing vendor stated them in this advisory; the linked CVE pages carry the independently enriched CVSS and SSVC assessments.

News Coverage

No coverage found in monitored research blogs or news feeds.

CVEs Referenced in This Publication

CVECVSSAffected
CVE-2024-0912 8.5 High Johnson Controls Software House C•CURE 9000 Under certain circumstances the Microsoft® Internet Information Server (IIS) used to host the C•CURE 9000 Web Server will log Microsoft Windows crede…

Named by the advisory itself. Each CVE links to its tracked detail page.

Vendors Named in This Publication

No KEV-catalogued vendors are named in this publication.