ICSA-26-020-02: Schneider Electric devices using CODESYS Runtime ↗ source

January 20, 2026 CISA ICS Advisory

Summary

Schneider Electric is aware of multiple vulnerabilities disclosed on CODESYS runtime system V3 communication server. Many vendors, including Schneider Electric, embed CODESYS in their offers. If successfully exploited, these vulnerabilities could result in a denial of service or, in some cases, in remote code execution on PacDrive controllers, Modicon Controllers M241 / M251 / M262 / M258 / LMC058 / LMC078 / M218 , HMISCU, the Simulation Runtime SoftSPS from EcoStruxure Machine Expert and EcoStruxure Microgrid Operation products. Failure to apply the mitigations provided below may result in denial of service and/or arbitrary remote code execution. CVE-2022-4046: In addition to the functionality described above, there are memory access functions that allow the PLC application code to read or write memory. These are not limited to the data memories that are assigned to it or allocated by it. For this reason, the PLC application code can potentially access the entire RAM memory of the CODESYS Control runtime process surrounding it. This could allow PLC programmers who have successfully authenticated themselves at the controller to execute PLC application code that can modify itself or read or write sensitive data of the CODESYS Control runtime process. CVE-2023-28355: The PLC application code executed by the CODESYS Control Runtime contains a checksum.

Advisory Details CISA ICS CSAF feed

Advisory ID
ICSA-26-020-02
Status
Final · version 10
Initial release
2023-07-11
Last revised
2026-01-20 (10 revisions)
Vendor
Schneider Electric
Critical infrastructure sectors
Commercial Facilities, Critical Manufacturing, Energy
Deployed
Worldwide
Vendor headquarters
France

Republished vendor advisory. This ICSA is a verbatim republication of Schneider Electric CPCERT SEVD-2023-192-04 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory.…

General Security Recommendations: We strongly recommend the following industry cybersecurity best practices. https://www.se.com/us/en/download/document/7EN52-0390/ * Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. * Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. * Place all controllers in locked cabinets and never leave them in the “Program” mode. * Never connect programming software to any network other than the network intended for that device. * Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. * Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. * Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. * When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.

For More Information: This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process. For further information related to cybersecurity in Schneider Electric’s products, visit the company’s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp

About Schneider Electric: Schneider’s purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and sustainability for all. We call this Life Is On. Our mission is to be the trusted partner in Sustainability and Efficiency. We are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart industries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep domain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation, software and services, delivering digital twins to enable profitable growth for our customers. We are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries to ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our meaningful purpose of a sustainable future for all.

Credit: Schneider Electric CPCERT

Affected products (20)
  • HMISCU Controller — <6.3.1, 6.3.1
  • Modicon Controller LMC078 — all versions
  • Modicon Controller M241 — <5.2.11.18, 5.2.11.18
  • Modicon Controller M251 — <5.2.11.18, 5.2.11.18
  • Modicon Controller M262 — <5.2.8.12, 5.2.8.12
  • Modicon Controller M258 — all versions
  • Modicon Controller LMC058 — all versions
  • Modicon Controller M218 — all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 — <1.76.14.1, 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert — <2.2, 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert — <6.3.1, 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series — <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series — <2.0_HF2
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime — 6.3_HF3
  • Vijeo Designer Basic — 2.0_HotFix_2
  • Harmony iPC series
  • Magelis XBT series — all versions
  • Easy Modicon M310 — <3.1.5.82, 3.1.5.82
  • Harmony P6 series
  • Vijeo Designer runtime — <6.3_SP2, 6.3_SP2
Revision history (10)
  • 2026-01-20 — v10: Initial Republication of Schneider Electric CPCERT SEVD-2023-192-04 advisory
  • 2025-12-09 — v9: Replaced advisory IDs with CVE IDs. Added vulnerability details, including CVE descriptions, CWE identifiers, CVSS scores, and vector strings. Corrected mappings of affected and fixed products for each CVE.
  • 2025-11-11 — v8: Remediation is available for Easy Modicon M310.
  • 2025-08-12 — v7: Remediations are available for Harmony iPC series and Harmony P6 series with Vijeo Designer.
  • 2024-06-11 — v6: Easy Modicon M310 is added to the list of products impacted
  • 2024-04-09 — v5: A remediation is now available for Easy Harmony HMIET6/HMIFT6, and Magelis HMIGXU series
  • 2024-03-12 — v4: A remediation is now available for HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series
  • 2024-01-09 — v3: Remediations added for different products.
  • 2023-08-08 — v2: New CODESYS advisories 2023-04 to 2023-09 added. Additional impacted product: Harmony and Easy Harmony, Vijeo Designer embedded in EcoStruxure Machine Expert.
  • 2023-07-11 — v1: Original Release

From CISA's machine-readable CSAF 2.0 advisory (JSON).

Vulnerabilities as Stated by the Advisory

CVEWeaknessCVSS v3Details
CVE-2022-4046 CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer 8.8 High CVE-2022-4046
In addition to the functionality described above, there are memory access functions that allow the PLC application code to read or write memory. These are not limited to the data memories that are assigned to it or allocated by it. For this reason, the PLC application code can potentially access the entire RAM memory of the CODESYS Control runtime process surrounding it. This could allow PLC programmers who have successfully authenticated themselves at the controller to execute PLC application code that can modify itself or read or write sensitive data of the CODESYS Control runtime process.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been rep…

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller LMC078 all versions
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • Modicon Controller M218 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • … and 2 more

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M251 to the latest Firmware and pr…

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

No fix planned: Schneider Electric´s Modicon LMC078 controllers have reached end of their life and are no longer commercially available. They have been replaced by the Modicon M262 controllers. We recommend our customers to migrate to the latest offer. Please contact your local Schneider Electric technical support for more information.

No fix planned: Schneider Electric’s Modicon M218 controllers have reached their end of life and are no longer commercially available. They have been replaced by the Modicon Easy M200 and Modicon M241 controllers. We recommend our customers to migrate to the latest offer. Please contact your local Schneider Electric technical support for more information.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2022-47379 CWE-787 Out-of-bounds Write 8.8 High CVE-2022-47379
After successful authentication, specific crafted communication requests can cause the CmpApp component to write attacker-controlled data to memory, which can lead to a denial-of-service condition, memory overwriting, or remote code execution.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been rep…

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M251 to the latest Firmware and pr…

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2022-47380 CWE-121 Stack-based Buffer Overflow 8.8 High CVE-2022-47380
After successful authentication, specific crafted communication requests can cause the CmpApp component to write attacker-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2022-47381 CWE-121 Stack-based Buffer Overflow 8.8 High CVE-2022-47381
After successful authentication, specific crafted communication requests can cause the CmpApp component to write attacker-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2022-47382 CWE-121 Stack-based Buffer Overflow 8.8 High CVE-2022-47382
After successful authentication, specific crafted communication requests can cause the CmpTraceMgr component to write attacker-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2022-47383 CWE-121 Stack-based Buffer Overflow 8.8 High CVE-2022-47383
After successful authentication, specific crafted communication requests can cause the CmpTraceMgr component to write attacker-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2022-47384 CWE-121 Stack-based Buffer Overflow 8.8 High CVE-2022-47384
After successful authentication, specific crafted communication requests can cause the CmpTraceMgr component to write attacker-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2022-47385 CWE-121 Stack-based Buffer Overflow 8.8 High CVE-2022-47385
After successful authentication, specific crafted communication requests can cause the CmpAppForce component to write attacker-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2022-47386 CWE-121 Stack-based Buffer Overflow 8.8 High CVE-2022-47386
After successful authentication, specific crafted communication requests can cause the CmpTraceMgr component to write attacker-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2022-47387 CWE-121 Stack-based Buffer Overflow 8.8 High CVE-2022-47387
After successful authentication, specific crafted communication requests can cause the CmpTraceMgr component to write attacker-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2022-47388 CWE-121 Stack-based Buffer Overflow 8.8 High CVE-2022-47388
After successful authentication, specific crafted communication requests can cause the CmpTraceMgr component to write attacker-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2022-47389 CWE-121 Stack-based Buffer Overflow 8.8 High CVE-2022-47389
After successful authentication, specific crafted communication requests can cause the CmpTraceMgr component to write attacker-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2022-47390 CWE-121 Stack-based Buffer Overflow 8.8 High CVE-2022-47390
After successful authentication, specific crafted communication requests can cause the CmpTraceMgr component to write attacker-controlled data to stack, which can lead to a denial-of-service condition, memory overwriting, or remote code execution.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been rep…

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M251 to the latest Firmware and pr…

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-3663 CWE-924 Improper Enforcement of Message Integrity During Transmission in a Communication Channel 8.8 High CVE-2023-3663
The Notification Center of the CODESYS Development System receives messages without ensuring that the message was not modified during transmission. This finally enables MITMs code execution when the user clicks the Learn More button.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2022-47391 CWE-1288 Improper Validation of Consistency within Input 7.5 High CVE-2022-47391
Crafted communication requests can cause the affected products to read internally from an invalid address, potentially leading to a denial-of-service condition.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-3662 CWE-427 Uncontrolled Search Path Element 7.3 High CVE-2023-3662
The CODESYS Development System is vulnerable to the execution of malicious binaries from the current working directory.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-3670 CWE-668 Exposure of Resource to Wrong Sphere 7.3 High CVE-2023-3670
CODESYS Scripting executes potentially malicious scripts saved by another user.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2022-47378 CWE-1288 Improper Validation of Consistency within Input 6.5 Medium CVE-2022-47378
After successful authentication, specific crafted communication requests with inconsistent content can cause the CmpFiletransfer component to read internally from an invalid address, potentially leading to a denial-of-service condition.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been rep…

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M251 to the latest Firmware and pr…

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2022-47392 CWE-1288 Improper Validation of Consistency within Input 6.5 Medium CVE-2022-47392
After successful authentication, specific crafted communication requests with inconsistent content can cause the CmpApp/CmpAppBP/CmpAppForce components to read internally from an invalid address, potentially leading to a denial-of-service condition.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2022-47393 CWE-822 Untrusted Pointer Dereference 6.5 Medium CVE-2022-47393
After successful authentication, specific crafted communication requests can cause the CmpFiletransfer component to dereference addresses provided by the request for internal read access, which can lead to a denial-of-service situation.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-28355 CWE-354 Improper Validation of Integrity Check Value 6.5 Medium CVE-2023-28355
The PLC application code executed by the CODESYS Control Runtime contains a checksum. This enables the CODESYS development system to check at login whether its loaded project matches the PLC application code executed on the controller. This checksum is not sufficient to reliably detect PLC application code that has been modified in memory or boot application files that have been manipulated.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller LMC078 all versions
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • Modicon Controller M218 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • … and 2 more

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

No fix planned: Schneider Electric´s Modicon LMC078 controllers have reached end of their life and are no longer commercially available. They have been replaced by the Modicon M262 controllers. We recommend our customers to migrate to the latest offer. Please contact your local Schneider Electric technical support for more information.

No fix planned: Schneider Electric’s Modicon M218 controllers have reached their end of life and are no longer commercially available. They have been replaced by the Modicon Easy M200 and Modicon M241 controllers. We recommend our customers to migrate to the latest offer. Please contact your local Schneider Electric technical support for more information.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-37545 CWE-20 Improper Input Validation 6.5 Medium CVE-2023-37545
After successful authentication as a user, specific crafted communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-ofservice condition.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-37546 CWE-20 Improper Input Validation 6.5 Medium CVE-2023-37546
After successful authentication as a user, specific crafted communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-ofservice condition.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-37547 CWE-20 Improper Input Validation 6.5 Medium CVE-2023-37547
After successful authentication as a user, specific crafted communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-ofservice condition.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-37548 CWE-20 Improper Input Validation 6.5 Medium CVE-2023-37548
After successful authentication as a user, specific crafted communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-ofservice condition.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-37549 CWE-20 Improper Input Validation 6.5 Medium CVE-2023-37549
After successful authentication as a user, specific crafted communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-ofservice condition.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-37550 CWE-20 Improper Input Validation 6.5 Medium CVE-2023-37550
After successful authentication as a user, specific crafted communication requests with inconsistent content can cause the CmpApp component to read internally from an invalid address, potentially leading to a denial-ofservice condition.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-37551 CWE-552 Files or Directories Accessible to External Parties 6.5 Medium CVE-2023-37551
After successful authentication as a user, specially crafted communication requests can utilize the CmpApp component to download files with any file extensions to the controller. In contrast to the regular file download via CmpFileTransfer, no filtering of certain file types is performed here. As a result, the integrity of the CODESYS control runtime system may be compromised by the files loaded onto the controller.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-37552 CWE-20 Improper Input Validation 6.5 Medium CVE-2023-37552
After successful authentication as a user, specific crafted communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of service condition.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-37553 CWE-20 Improper Input Validation 6.5 Medium CVE-2023-37553
After successful authentication as a user, specific crafted communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of service condition.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-37554 CWE-20 Improper Input Validation 6.5 Medium CVE-2023-37554
After successful authentication as a user, specific crafted communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of service condition.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-37555 CWE-20 Improper Input Validation 6.5 Medium CVE-2023-37555
After successful authentication as a user, specific crafted communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of service condition.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-37556 CWE-20 Improper Input Validation 6.5 Medium CVE-2023-37556
After successful authentication as a user, specific crafted communication requests with inconsistent content can cause the CmpAppBP component to read internally from an invalid address, potentially leading to a denial-of service condition.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-37557 CWE-787 Out-of-bounds Write 6.5 Medium CVE-2023-37557
After successful authentication as a user, specific crafted communication requests can cause the CmpAppBP component to overwrite a heap-based buffer, which can lead to a denial-of-service condition.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-37558 CWE-20 Improper Input Validation 6.5 Medium CVE-2023-37558
After successful authentication as a user, specific crafted communication requests with inconsistent content can cause the CmpAppForce component to read internally from an invalid address, potentially leading to a denial-of service condition.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-37559 CWE-20 Improper Input Validation 6.5 Medium CVE-2023-37559
After successful authentication as a user, specific crafted communication requests with inconsistent content can cause the CmpAppForce component to read internally from an invalid address, potentially leading to a denial-of service condition.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

CVE-2023-3669 CWE-307 Improper Restriction of Excessive Authentication Attempts 3.3 Low CVE-2023-3669
The Notification Center of the CODESYS Development System receives messages without ensuring that the message was not modified during transmission. This finally enables MITMs code execution when the user clicks the Learn More button.

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the en… ↗

Vendor fix: Modicon Controller M241 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Vendor fix: Modicon Controller M251 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-exp… ↗

Affected, fixed & timeline

Affected:

  • HMISCU Controller <6.3.1
  • Modicon Controller M241 <5.2.11.18
  • Modicon Controller M251 <5.2.11.18
  • Modicon Controller M262 <5.2.8.12
  • Modicon Controller M258 all versions
  • Modicon Controller LMC058 all versions
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 <1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert <2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert <6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series <6.3_HF3
  • Easy Harmony HMIET6/HMIFT6 Magelis HMIGXU series <2.0_HF2
  • Magelis XBT series all versions
  • Easy Modicon M310 <3.1.5.82
  • CSAFPID-0030
  • CSAFPID-0032

Fixed in:

  • HMISCU Controller 6.3.1
  • Modicon Controller M241 5.2.11.18
  • Modicon Controller M251 5.2.11.18
  • Modicon Controller M262 5.2.8.12
  • PacDrive 3 Controllers: LMC Eco/Pro/Pro2 1.76.14.1
  • SoftSPS embedded in EcoStruxure Machine Expert 2.2
  • Vijeo Designer embedded in EcoStruxure Machine Expert 6.3.1
  • Harmony (Formerly Magelis) HMIGK/HMIGTO/HMIGTU/HMIGTUX/HMISTU series iPC series with Vijeo Designer runtime 6.3_HF3
  • Vijeo Designer Basic 2.0_HotFix_2
  • CSAFPID-0031
  • CSAFPID-0033
  • Easy Modicon M310 3.1.5.82

No fix planned: Schneider Electric’s Magelis XBT series have reached their end of commercialization. Magelis XBTGT/XBTGK offers have been replaced by HMIGTO/HMIGTU/HMIGK. We recommend our customers to migrate to the latest offers. For Magelis XBT series that haven't been replaced, please contact your local Schneider Electric technical support for more information.

Vendor fix: Modicon Controller M262 Firmware delivered with Machine Expert v2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2 of Machine Expert. Update Modicon Controller M262 to the latest firmware and pr…

Vendor fix: PacDrive 3 Controllers LMC Eco/Pro/Pro2 Firmware delivered with Machine Expert V2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to V2.2 of Machine Expert. Update PacDrive 3 Controllers: LMC Eco/Pro/P…

Vendor fix: Version 6.3.1 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeodesigner-hmi-software/#software-and-firmware On the engineering workstation, update to v6.3.1 of Vijeo Designer.

Vendor fix: SoftSPS component has been removed from Machine Expert V2.2. Machine Expert can be updated through the Schneider Electric Software Update (SESU) application.

Mitigation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Use encrypted communication links. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide mitigations through the activation of project encryption in the Enhanced Security Sett…

Mitigation: • Enable the optional ‘Implicit Checks’ on logic applications. • Avoid use of the POINTER data type and MEMMOVE instructions, especially on untrusted inputs. • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from outside. • Use firewalls to protect and separate the control system network from other networks. • Use VP…

Vendor fix: Version 3.1.5.82 includes a fix for this vulnerability and can be download here: https://www.se.com/ww/en/product-range/268959560-easy-modicon-m310 As an alternative, contact your Schneider Electric Customer Care Center to obtain the firmware. To complete the update, connect to M310 and download the firmware using EcoStruxureTM Motion Expert.

Vendor fix: Version 6.3 HF3 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix. On the engineering workstation, update to v6.3 HF3 of Vijeo Design…

Vendor fix: Vijeo Designer Basic v2.0 HotFix 2 includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the installer. To complete the update, connect to Harmony HMI and download the firmware using Vijeo Designer Basic.

Vendor fix: Version 6.3 SP2 of Vijeo Designer includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/1054-vijeo-designer-hmi-software/#software-and-firmware As an alternative, please contact your Schneider Electric Customer Care Center to obtain the Fix. For additional details, please refer to the supp…

Mitigation: Customers should immediately apply the following mitigations to reduce the risk of exploitation: • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use.• Restrict access to programming ports, typically UDP/1740, TCP/11740 and TCP/484.• Use controllers and devices only in a protected environment to minimize ne…

Scores and weakness types are as CISA or the republishing vendor stated them in this advisory; the linked CVE pages carry the independently enriched CVSS and SSVC assessments.

News Coverage

No coverage found in monitored research blogs or news feeds.

CVEs Referenced in This Publication

CVECVSSAffected
CVE-2022-4046 8.8 High CODESYS CODESYS Control for BeagleBone SL In CODESYS Control in multiple versions a improper restriction of operations within the bounds of a memory buffer allow an remote attacker with user …
CVE-2022-47379 8.8 High CODESYS CODESYS Control RTE (SL) An authenticated, remote attacker may use a out-of-bounds write vulnerability in multiple CODESYS products in multiple versions to write data into me…
CVE-2022-47380 8.8 High CODESYS CODESYS Control RTE (SL) An authenticated remote attacker may use a stack based  out-of-bounds write vulnerability in multiple CODESYS products in multiple versions to write …
CVE-2022-47381 8.8 High CODESYS CODESYS Control RTE (SL) An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in multiple CODESYS products in multiple versions to write d…
CVE-2022-47382 8.8 High CODESYS CODESYS Control RTE (SL) An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in…
CVE-2022-47383 8.8 High CODESYS CODESYS Control RTE (SL) An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products i…
CVE-2022-47384 8.8 High CODESYS CODESYS Control RTE (SL) An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in…
CVE-2022-47385 8.8 High CODESYS CODESYS Control RTE (SL) An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpAppForce Component of multiple CODESYS products i…
CVE-2022-47386 8.8 High CODESYS CODESYS Control RTE (SL) An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products i…
CVE-2022-47387 8.8 High CODESYS CODESYS Control RTE (SL) An authenticated remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products in…
CVE-2022-47388 8.8 High CODESYS CODESYS Control RTE (SL) An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products i…
CVE-2022-47389 8.8 High CODESYS CODESYS Control RTE (SL) An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products i…
CVE-2022-47390 8.8 High CODESYS CODESYS Control RTE (SL) An authenticated, remote attacker may use a stack based out-of-bounds write vulnerability in the CmpTraceMgr Component of multiple CODESYS products i…
CVE-2023-3663 8.8 High CODESYS CODESYS Development System In CODESYS Development System versions from 3.5.11.20 and before 3.5.19.20 a missing integrity check might allow an unauthenticated remote attacker t…
CVE-2022-47391 7.5 High CODESYS CODESYS Control RTE (SL) In multiple CODESYS products in multiple versions an unauthorized, remote attacker may use a improper input validation vulnerability to read from inv…
CVE-2023-3662 7.3 High CODESYS CODESYS Development System In CODESYS Development System versions from 3.5.17.0 and prior to 3.5.19.20 a vulnerability allows for execution of binaries from the current working…
CVE-2023-3670 7.3 High CODESYS CODESYS Development System In CODESYS Development System 3.5.9.0 to 3.5.17.0 and CODESYS Scripting 4.0.0.0 to 4.1.0.0 unsafe directory permissions would allow an attacker with …
CVE-2022-47378 6.5 Medium CODESYS CODESYS Control RTE (SL) Multiple CODESYS products in multiple versions are prone to a improper input validation vulnerability. An authenticated remote attacker may craft spe…
CVE-2022-47392 6.5 Medium CODESYS CODESYS Control RTE (SL) An authenticated, remote attacker may use a improper input validation vulnerability in the CmpApp/CmpAppBP/CmpAppForce Components of multiple CODESYS…
CVE-2022-47393 6.5 Medium CODESYS CODESYS Control RTE (SL) An authenticated, remote attacker may use a Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability in multiple version…
CVE-2023-37545 6.5 Medium CODESYS CODESYS Control for BeagleBone SL In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with in…
CVE-2023-37546 6.5 Medium CODESYS CODESYS Control for BeagleBone SL In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with in…
CVE-2023-37547 6.5 Medium CODESYS CODESYS Control for BeagleBone SL In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with in…
CVE-2023-37548 6.5 Medium CODESYS CODESYS Control for BeagleBone SL In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with in…
CVE-2023-37549 6.5 Medium CODESYS CODESYS Control for BeagleBone SL In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with in…
CVE-2023-37550 6.5 Medium CODESYS CODESYS Control for BeagleBone SL In multiple Codesys products in multiple versions, after successful authentication as a user, specific crafted network communication requests with in…
CVE-2023-37551 6.5 Medium CODESYS CODESYS Control for BeagleBone SL In multiple Codesys products in multiple versions, after successful authentication as a user, specially crafted network communication requests can ut…
CVE-2023-37552 6.5 Medium CODESYS CODESYS Control for BeagleBone SL In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with in…
CVE-2023-37553 6.5 Medium CODESYS CODESYS Control for BeagleBone SL In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with in…
CVE-2023-37554 6.5 Medium CODESYS CODESYS Control for BeagleBone SL In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with in…
CVE-2023-37555 6.5 Medium CODESYS CODESYS Control for BeagleBone SL In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with in…
CVE-2023-37556 6.5 Medium CODESYS CODESYS Control for BeagleBone SL In multiple versions of multiple Codesys products, after successful authentication as a user, specific crafted network communication requests with in…
CVE-2023-37557 6.5 Medium CODESYS CODESYS Control for BeagleBone SL After successful authentication as a user in multiple Codesys products in multiple versions, specific crafted remote communication requests can cause…
CVE-2023-37558 6.5 Medium CODESYS CODESYS Control for BeagleBone SL After successful authentication as a user in multiple Codesys products in multiple versions, specific crafted network communication requests with inc…
CVE-2023-37559 6.5 Medium CODESYS CODESYS Control for BeagleBone SL After successful authentication as a user in multiple Codesys products in multiple versions, specific crafted network communication requests with inc…
CVE-2023-3669 3.3 Low CODESYS CODESYS Development System A missing Brute-Force protection in CODESYS Development System prior to 3.5.19.20 allows a local attacker to have unlimited attempts of guessing the …